CT105-868M - LoRaWAN Current Transformer
Product Description
CT105-868M LoRaWAN Smart Current Transformer is a non-invasive split-core current monitoring solution intended for indoor electrical distribution and industrial facilities.
The CT105 has a 500 A RMS rated primary current.
Its 36.5 mm conductor opening is suitable for high-current feeders, large motors, chillers and industrial electrical panels where remote current monitoring is required.
CT105 measures RMS current on a conductor at a 50–60 Hz supply frequency.
Applications
Product Specifications
| Brand / OEM | Milesight |
| Model | CT105-868M |
| Device Type | LoRaWAN® Smart Current Transformer |
| Measured Parameter | RMS AC current |
| Rated Primary Current (CT105) | 500 Arms |
| Rated Secondary Current (CT105) | 150 mArms |
| Grid Frequency | 50–60 Hz |
| Sampling Frequency | 3.3 kHz |
| Sampling / Quick Alarm Rate | Up to 1 second (depending on mode) |
| Measurement Accuracy | ±1% (>5 Arms); ±3% (≤5 Arms) |
| Resolution | 1 mA |
| Minimum Reporting Current (1-minute reporting) | 5 Arms when powered by the measured conductor |
| Minimum Reporting Current (10-minute reporting) | 4.7 Arms when powered by the measured conductor |
| Low-Current Measurement | 5 V USB Type-C power may be required below conductor-powered reporting threshold |
| Accumulated Current | Cumulative ampere-hour / current data reporting supported |
| Optional Temperature Sensor | USB Type-C-connected NTC cable temperature sensor |
| Temperature Sensor Measurement Range | −20°C to +100°C |
| Temperature Sensor Accuracy | ±1% (as specified by Milesight) |
| Wireless Communication | LoRaWAN® |
| Requested Frequency | EU868 / 868 MHz |
| Other Family Regional Versions | CN470, IN865, RU864, US915, AU915, KR920, AS923-1/2/3/4; variant-dependent |
| LoRaWAN Activation / Class | OTAA / ABP, Class A |
| Antenna Interface | 1 × 50 Ω SMA female connector |
| Transmit Power at 868 MHz | 16 dBm |
| Receiver Sensitivity | Approximately −137 dBm |
| Configuration | USB Type-C console or LoRaWAN downlink |
| Remote Firmware Upgrade | FUOTA (Firmware Update Over the Air), when supported by network |
| Alarms | Threshold and overrange alarms |
| Reboot Button | 1 |
| Status / Alarm LED | 1 |
| USB Interface | USB Type-C for 5 V power, configuration, console or cable temperature input |
| Power | Induced-current self-power or 5 V USB Type-C |
| Battery Requirement | No battery |
| Insulation Voltage | 2.5 kVac RMS (1 mA / 1 min) |
| Housing Material / Colour | Blue PBT + PC, UL94 V-0 |
| Ingress Protection | IP30; indoor use |
| System Operating Temperature | −20°C to +70°C |
| Storage Temperature | −25°C to +80°C |
| Relative Humidity | ≤95%, non-condensing |
| Clamp Dimensions (CT105) | 68 × 86 × 41.8 mm |
| Conductor Hole Diameter | Ø 36.5 mm |
| Transceiver Dimensions | 38 × 34.5 × 16 mm |
| Transceiver Weight | 13.05 g |
| CT105 Clamp Weight | 276.75 g |
| Extension / Connection Cable | Approx. 1 m |
| Mounting | Clamp on individual test conductor; cable-tie mounted radio transceiver |
| Listed Regulatory Approvals | CE, FCC, UL508 |
| Seller Warranty | 1 year |
| Use in India | Confirm EU868 compatibility, or specify correct IN865 variant for Indian LoRaWAN networks |
Product Features
- Measures AC RMS current of a single monitored conductor; CT105 model has rated primary current of 500 Arms.
- Secondary current rating is 150 mArms; specified working frequency is 50–60 Hz.
- Sampling frequency is 3.3 kHz with up to one-second sensing/reporting for rapid monitoring.
- Manufacturer-specified accuracy is ±1% for current greater than 5 Arms and ±3% at or below 5 Arms.
- Current measurement resolution is 1 mA.
- Split-core clamp allows measuring one conductor without disconnecting the circuit; installation must follow qualified electrical safety procedures.
- CT105 clamp opening diameter is 36.5 mm; clamp dimensions are 68 × 86 × 41.8 mm.
- Supports accumulation of measured current over time and cumulative ampere-hour reporting; current alone is not a direct calibrated kWh reading.
- Reports current remotely via LoRaWAN gateways and network servers for dashboard analysis.
- Configurable threshold alarms and overrange alarms support feeder load monitoring and condition alerts.
- Current-induced energy harvesting supplies the sensor without batteries in normal current conditions.
- USB Type-C 5 V supplementary supply can support low-current measurements or bench commissioning.
- For conductor-powered operation, the official CT10x datasheet shows 5 Arms minimum reporting current at one-minute interval, or 4.7 Arms at ten-minute interval for CT105.
- Optional external USB-connected NTC sensor measures cable temperature from −20°C to +100°C with stated ±1% accuracy.
- An external antenna connects through one 50 Ω SMA female connector.
- EU868 variant transmit power is 16 dBm, and radio sensitivity is approximately −137 dBm.
- LoRaWAN OTAA and ABP activation with Class A uplink/downlink communications.
- Local setup via USB Type-C and remote configuration via LoRaWAN downlink.
- Firmware updates over the air (FUOTA) are supported where compatible infrastructure is available.
- One reboot button and one status/alarm LED indicator are provided.
- Transceiver measures 38 × 34.5 × 16 mm; it may be mounted using a cable tie and located for improved radio coverage.
- CT105 includes a clamp/transceiver assembly with approximately 1 m connection cable; verify factory configuration and packaging.
- Transceiver / CT system operating range is −20°C to +70°C, humidity ≤95% non-condensing; enclosure rated IP30.
- Manufacturer datasheet lists CE, FCC and UL508 regulatory approvals; no hazardous-area explosion-proof certification is claimed.
- CT105-868M EU868 radio variant differs from IN865; confirm suitability and radio approvals for Indian installations.
Package Includes
- 1 × Milesight CT105-868M Smart Current Transformer with CT105 500 A clamp and LoRaWAN transceiver
- 1 × USB Type-C NTC temperature-sensor accessory (listed in Milesight CT10x hardware packing guide; verify in supplier's final pack)
- 1 × standard LoRaWAN stubby antenna (antenna length/type may vary by supplied kit)
- 1 × quick guide and warranty card where provided by OEM
- Optional magnetic antenna and other special accessories are not automatically included; check the supplier packing list before dispatch
Frequently Asked Questions
What does the Milesight CT105-868M Current Transformer measure?
What is the rated current, clamp opening, and measurement accuracy of CT105?
Does the CT105 need a battery, and how does it work at low currents?
Can CT105-868M be remotely configured and used with an Indian LoRaWAN network?
What comes with the CT105 sensor, and how should it be installed?
Other Information
Warranty Information
1 Year Seller Warranty
This item is covered with a standard warranty of 1 year from the time of delivery against manufacturing defects only. This warranty is given for the benefit of TwoElectrons customers from any kind of manufacturing defects. Replacement will be done against manufacturing defects.
What Voids Warranty
If the product is subject to misuse, tampering, static discharge, accident, water or fire damage, use of chemicals & soldered or altered in any way.
Shipping & Returns Policy
Shipping Policy:
- In-stock items are delivered within 7-10 working days for orders within India. Delivery varies based on location and courier service.
- In-stock items are delivered within up to 20 working days for orders outside India. Delivery varies based on location and courier service.
- If the item is out of stock, you can still place an order. The estimated delivery time will be notified to you by email.
Return & Refund Policy:
- Return window: 7 days from receipt unless stated otherwise.
- No refunds or replacements after the return window.
- Returns are accepted only for non-working or damaged products.
- Initiate return requests from here: Return Request or contact us at 09831070550.
- Refunds are processed within 3-4 working days after inspection and approval.
Main Features
- CT105-868M: 500 Arms LoRaWAN® smart split-core current transformer for indoor electrical systems
- Non-invasive clamp-on current measurement, designed for installation without disconnecting conductors
- Large 36.5 mm conductor opening for industrial feeders, motors and high-current circuits
- 50–60 Hz RMS current measurement with up to 3.3 kHz sampling
- ±1% accuracy above 5 Arms and ±3% at or below 5 Arms, with 1 mA resolution
- Self-powered from induced conductor current; alternatively 5 V input via USB Type-C
- Reports RMS current and cumulative ampere-hour / accumulated current metrics
- Supports configurable current threshold and measurement overrange alerts
- Fast sampling (up to 1-second interval) for timely readings and alarms
- EU868 / 868 MHz LoRaWAN® regional radio variant; OTAA/ABP Class A
- Configuration via USB Type-C console or supported LoRaWAN downlink
- Optional NTC cable temperature sensor connection via USB Type-C
- Supports Firmware Update Over the Air (FUOTA)
- Blue PBT+PC UL94 V-0 construction with IP30 indoor protection
- Compatible with Milesight LoRaWAN gateways, standard LoRaWAN network servers and Milesight Development Platform
Lead time
| QUANTITY | DISPATCH |
|---|---|
| 1-10 units |
Order from India: 7-10 working days Order outside India: Up to 20 working days |
| 10+ units | To be negotiated |
Protections for this product
Delivery via TwoElectrons Logistics
We aim to deliver your order within the scheduled dates, but delays may occur due to unforeseen circumstances.
Secure Payments
Your payment information is safe with us. TwoElectrons.com uses SSL encryption to ensure secure and reliable transactions.
Standard Refund Policy
You're covered! If your order doesn't ship, arrives incomplete, or has any product issues, you can claim a full refund.